Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T03CM01068
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2003 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection 0000* | |
| 07/30/2003 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection 0000* 1) FITXTURE "A" IS A 70W HPS WITH BULB CUT OFF. PLANS CALL FOR 150W HPS FULLY SHEILDED. 2) PLANS CALL FOR A SERVICE AND PANEL. WE HAVE ??? PLEASE REVISE BOTH SETS OF PLANS TO REFLECT WORK INSTALLED. | |
| 07/23/2003 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection 0999* | |
| 06/03/2003 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | ||
| 06/02/2003 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection 0000* | |
| 05/29/2003 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection 0000*/ 1) BOND CONDUCTOR/JUMPER IS NEEDED FOR BUSHINGS IN GOTTIER-SIZE PER 250-66 AND 250-102 2) IF A BACK FEED BREAKER IS OPEN IT MUST HAVE A MANUFACTURERS HOLDOWN DEVICE |