Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
IVRS - Inspection 0000* |
| 07/30/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1) FITXTURE "A" IS A 70W HPS WITH BULB CUT OFF. PLANS CALL FOR 150W HPS FULLY SHEILDED. 2) PLANS CALL FOR A SERVICE AND PANEL. WE HAVE ??? PLEASE REVISE BOTH SETS OF PLANS TO REFLECT WORK INSTALLED. |
| 07/23/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Denied |
IVRS - Inspection 0999* |
| 06/03/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Not ready for Inspection |
|
| 06/02/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 05/29/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) BOND CONDUCTOR/JUMPER IS NEEDED FOR BUSHINGS IN GOTTIER-SIZE PER 250-66 AND 250-102 2) IF A BACK FEED BREAKER IS OPEN IT MUST HAVE A MANUFACTURERS HOLDOWN DEVICE |