Permit: T03CM01068

Parcel: 133153330


Addresses:

1889 N KOLB RD


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T03CM01068

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2003 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection 0000*
07/30/2003 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection 0000* 1) FITXTURE "A" IS A 70W HPS WITH BULB CUT OFF. PLANS CALL FOR 150W HPS FULLY SHEILDED. 2) PLANS CALL FOR A SERVICE AND PANEL. WE HAVE ??? PLEASE REVISE BOTH SETS OF PLANS TO REFLECT WORK INSTALLED.
07/23/2003 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0999*
06/03/2003 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection
06/02/2003 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection 0000*
05/29/2003 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection 0000*/ 1) BOND CONDUCTOR/JUMPER IS NEEDED FOR BUSHINGS IN GOTTIER-SIZE PER 250-66 AND 250-102 2) IF A BACK FEED BREAKER IS OPEN IT MUST HAVE A MANUFACTURERS HOLDOWN DEVICE