Permit: T03CM01051

Parcel: 10709092A


Addresses:

515 W KELSO ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/08/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000* 1) PVC COMPRESSION REPAIR COUPLING REPLACED WITH SOLVENT WELD COUPLING-O.K. 2) OK TO COVER. 3) REDLINE "AS BUILTS" TO REFLECT INSTALLATION AND LOCATION.
07/07/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*
07/06/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000* 1) COPPER WATER LINE UNDER BLDG( RE-ROUTED) OK PRESSURE TEST OK. SIL???JOINTS OK. 2) WHY DID YOU USE A REPAIR COUPLING AT THE CONNECTION TO EXISTING INSTEAD OF A SOLVENT WELD COUPLING? THERE IS NO CONDITION THAT WOULD PREVENT YOU USING THE CORRECT FITTING. COMPRESSION FITTING NOT APPROVED
07/02/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION
06/26/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000* SEWER CONNECTION TO CLAY OK. OK TO BACKFILL.
06/25/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) N/H UNDERGROUND SUBJECT TO REVISED APPROVAL PLAN 2) OK TO COVER 3) NEED TO SEE TIE-IN AT EXISTING CLAY 4) NEED TO SEE WATER CONNECTIONS
06/24/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999* PLANS PERMITS AND SPEC BOOK TO BE ON JOB SITE AT ALL TIMES UNABLE TO MAKE INSPECTION WITHOUT ALLL REQUIRED DOCUMENTS.