Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/06/2004 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950*/ 1) DUCT WORK RESTRICTED TO TIGHT OF BEND RADIUS. MUST BE 1 DUCT DIAMETER RADIUS 2) PLAN CALLS FOR METAL DUCT WORK HAVE PLAN REVISED AND APPROVED FOR AS BUILT 3) GAS LINES NOT INSTALLED 4) NO DWV PLUMBING WATER TEST TO ROOF 5) PLAN CALLS FOR GAS FURNACE-HOUSE APPEARS ALL ELECTRIC REVISE PLAN FOR AS BUILT AND HAVE APPROVED 6) LPI'S HAVE 2 1/2" HOLES DRILLED WITHIN 12" OF BEARING POINTS IN GARAGE. PROVIDE LPI ENGINEERING 7) BEAMS MUST BEAR ON POSTS, HEADERS AND STUDS 8) FIRE STOP DROP CEILING AT SOFFITS KITCHEN/DINING ROOM 9) MASTER BATH LAV DIRT ARM CANNOT EXCEED 1 1/2" DIAMETER OF 42" IN LENGTH TO VENT 10) M/TUB NOT INSTALLED 11) SUPPORT 4 ? ELECTRIC SWITCH BOXES TWO ENDS 12) GAS LOG AT FIREPLACE REQUIRES GAS SHUT OFF VALVE 13) BEARING STUD NOTCHED GREATER THAN 25 PERCENT FIREPLACE 14) WHERE IS GAS SUPPLY LINE 15) BOND GAS LINE 16) STOPPED INSPECTION. TOO MANY ITEMS |