Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2004 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/14/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) DOUBLE RAFTER AT BACK PATIO MISSING HANGERS 2) LEDGER CLIPS AROUND ENTIRE HOUSE MISSING NAILS 3) HOLDOWN LEFT SIDE OF FRONT DOOR WINDOW NOT INSTALLED PER PLAN | |
| 04/13/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) PROVIDE PLY CLIPS PER PLAN 2) PROVIDE MID HT. BLKS PER PLAN 3) PROVIDE HANGERS AT PORCH RAFTERS 45 DEGREE 4) STRAPS NEEDED AT BEAM TO POST CONNECTIONS 5) MULTIPLE ITEMS MISSING CONCERNING POST TO BEAM CONNECTIONS. MUST PROVIDE CONTINOUS POSITIVE CONNECTIONS | |
| 03/25/2004 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) OK AT LEDGERS PENDING PORCHES |