Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* 1) SOIL WATER TEST FOR VENT & DISCHARGER LINE IS OK. 2) OK TO BACKFILL TRENCH |
| 07/07/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* MUST PROVIDE WATER TEST ON VENT & DISCHARGE DRAIN |