Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM01008

Parcel: 126050300


Addresses:

4044 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM01008

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
06/26/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) FINISH ITEM #8, 11 AND 12 OF PREVIOUS INSPECTION 2) WAITING ON APPROVED PLANS AND LETTERS
06/20/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) PLEASE VERIFY IF WATER HEATER IS SUPPLIED AS CORD CONNECTED FROM MANUFACTURE 2) TIGHTEN LOOSE M/C FITTINGS 3) PROPERLY INSTALL GROUND EQUIPMENT CONDUCTOR AT BOX 4) PROTECT CONDUCTORS ENTERING LIGHT FIXTURES 5) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE 370.20 6) FILL UNUSED OPENINGS IN FIXTURES 7) CONDUCTOR NOT PROPERLY FASTENED AT RECEPTACLE 8) HAVE PLANS APPROVED BY CITY AND PROVIDE LETTERS AS PER PREVIOUS INSPECTIONS 9) TIGHTEN LOOSE CONDUIT FITTINGS 10) BONDING JUMBPER TO BE SIZED PER 250.102 AND 250.66 11) GROUNDING ELECTRODE CONDUCTOR TO ATTACH AT GROUNDED TERMINAL 12) PLANS NOT REFLECTIVE OF SERVICE EQUIPMENT 13) LIGHTING TO MEET LIGHTING CODE 14) RECEPTACLES WITH #2 WIRE TO HAVE SCREWS