Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01008
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
06/26/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) FINISH ITEM #8, 11 AND 12 OF PREVIOUS INSPECTION 2) WAITING ON APPROVED PLANS AND LETTERS | |
06/20/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) PLEASE VERIFY IF WATER HEATER IS SUPPLIED AS CORD CONNECTED FROM MANUFACTURE 2) TIGHTEN LOOSE M/C FITTINGS 3) PROPERLY INSTALL GROUND EQUIPMENT CONDUCTOR AT BOX 4) PROTECT CONDUCTORS ENTERING LIGHT FIXTURES 5) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE 370.20 6) FILL UNUSED OPENINGS IN FIXTURES 7) CONDUCTOR NOT PROPERLY FASTENED AT RECEPTACLE 8) HAVE PLANS APPROVED BY CITY AND PROVIDE LETTERS AS PER PREVIOUS INSPECTIONS 9) TIGHTEN LOOSE CONDUIT FITTINGS 10) BONDING JUMBPER TO BE SIZED PER 250.102 AND 250.66 11) GROUNDING ELECTRODE CONDUCTOR TO ATTACH AT GROUNDED TERMINAL 12) PLANS NOT REFLECTIVE OF SERVICE EQUIPMENT 13) LIGHTING TO MEET LIGHTING CODE 14) RECEPTACLES WITH #2 WIRE TO HAVE SCREWS |