Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM01008
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2003 | ELECTRIC - INTERMEDIATE | Approved | ||
05/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK HARD CEILING MUSIC ROOMS AND HALL | |
05/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALLS EAST & WEST SALES AREA, 2 MUSIC ROOM, NEW EXIT CORRIDOR, NORTH STOCK ROOM, TOILT & UTILITY ROOM 1.) MAKE NOTE OF #5 ON SPEC SHEET FOR HOME RUNS. |
|
05/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) TIGHTEN ALL LOOSE FITTINGS 2) REPLACE BROKEN FITTINGS 3) PLEASE FILL UNUSED OPENINGS IN BOXES 4) PLEASE PROVIDE LETTER AUTOWRITING-USE OF M/C CABLE 5) PLANS CALL FOR 2 1/2" CONDUIT FOR FEEDERS WE HAVE 2" INSTALLED |