Permit: T03CM00989

Parcel: 11809041B

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/24/2006 BUILDING - FINAL Approved IVRS - Inspection :*
08/22/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) ARC FAULT CIRCUIT NOT WORKING PROOPERLY IN ALL BEDROOMS
08/21/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MASTER BEDROOM ARC FAULT DUES NOT TEST
2) POST ADDRESS VISIBLE FROM STREET
3) LOWER CLEANOUTS TO GRADE
4) PROVIDE 4" CLEARANCE FROM STUCCO WEEP SCREED EXTERIOR GRADE
5) SEAL WATER HEATER B-VENT AT LID
6) SECURE DISHWASHER DRAIN HOSE TO HIGHEST POINT UNDER CABINET
7) BEDROOMS ARC FAULT DO NOT TEST
08/18/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ARC FAULT SMOKIES
2) 15 AMP BREAKER REQUIRED ON ? AWG WIRE
3) BUBBLE COVERS ON EXTERIOR OUTLETS
4) EXTERIOR GRADE MUST SLOPE 6" AWAY FROM HOUSE
5) SINGLE OUTLET AT WASHER
6) PROVIDE AIR ENTRANCE FOR B-VENT
7) DRIP LEG AT WATER HTR
8) POWER TO BLUE ROOM ?
9) ANTI-TIP ON RANGE
10) POWER TO DISHWASHER
11) GROUND METAL BOX OVER MICROWAVE
12) DRIP LEG AT FURNACE