Permit: T03CM00989

Parcel: 11809041B

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
10/06/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/04/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) ALL BUT PORCH COLUMNS 2) HOUSE OK TO DRY IN
08/03/2004 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*/ 1) NOT READY PER OWNER
08/02/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :PLAN CALLS FOR ANCHORR AND POST BASES FOR PORCH COLUMNS PER 4/A1 BUILD OR HAVE PLAN REVISED TO AS BUILT
POST TO BEAM CONNECTION REQUIRES 3/8" PLATE CONNECTION PER 2/A3 LAG BOLT USED BUILD TO PLAN OR REVISE PLAN
PROVIDE CITY APPROVED DETAIL FOR PORCH LEDGER TO HOUSE CONNECTION
JOIST HAMPER MISSING SE CORNER AND NE CORNER
H2.5 CLIPS REQUIRED ON RAFTERS TO BEARING WALL
RAFTER ON WEST END OF EAST ADDITION RAFTER KNOTCHED GREATER THAN 25%
BEARING WALLS REQUIRE 1/2" ANCHOR BOLTS AT EACH END AND EVERY 32" OC PER 2/A1
HOLD DOWNS NOT NAILED
SHEATH OR CLIP ALL STUDS
LEDGES MISSING AT A34 CLIPS
SPLICED RAFTERS NOT ALLOWED 12 FT SPAN
STRAP MID PT RAFTERS TO EXISTING HOUSE WALL
STUDS MAX SPACE ALLOWD 24" OC