Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 11/25/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TEMP C OF O 2) PLEASE COMPLETE #3 OF PREVIOUS INSPECTION 3) RECEIVED LETTER FOR NURSE CALL SYSTEM |
| 11/21/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE DRAWINGS/LETTER EXPLAINING OR NOTING 120V NURSE CALL SYSTEM-CIRCUITS, LOCATION AND FUNCTION 2) BOXES WITH MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 370.20, METAL NOT APPROVED 3) WILL NEED TO VERIFY EQUIPMENT LISTING 4) EXHAUST FANS: USE APPROVED FITTINGS AND PROTECT SEAL TITE FROM SHARP METAL EDGES 5) RECEIVED LETTERS AS REQUESTED 6) OK TEMP C OF O SUBJECT TO DETERMINATION OF INSPECTIONS MANAGER |
| 11/19/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* NURSES STATION |