Permit: T03CM00984

Parcel: 110103060


Addresses:

3190 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/19/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
11/25/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK TEMP C OF O 2) PLEASE COMPLETE #3 OF PREVIOUS INSPECTION 3) RECEIVED LETTER FOR NURSE CALL SYSTEM
11/21/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLEASE PROVIDE DRAWINGS/LETTER EXPLAINING OR NOTING 120V NURSE CALL SYSTEM-CIRCUITS, LOCATION AND FUNCTION 2) BOXES WITH MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 370.20, METAL NOT APPROVED 3) WILL NEED TO VERIFY EQUIPMENT LISTING 4) EXHAUST FANS: USE APPROVED FITTINGS AND PROTECT SEAL TITE FROM SHARP METAL EDGES 5) RECEIVED LETTERS AS REQUESTED 6) OK TEMP C OF O SUBJECT TO DETERMINATION OF INSPECTIONS MANAGER
11/19/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* NURSES STATION