Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T03CM00981
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2003 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
07/02/2003 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SECURE LIQUID TIGHT 8" FROM DISCONNECT 2) LEVEL THE UNIT 3) TURN MAXIMUM OVER CURRENT 60/60 MINIMUM CLR AMPACITY 56.1 YOU HAVE 40/40 FUSES, 50 AMP CIRCUIT FROM THE SERVICE 5) HOLE IN ROOFING AT SCUPPER PASSING THRU PARPAPET 6) 3 LABELS ON UNIT | |
06/30/2003 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NEED GFCI AT LAUNDRY SINK 2) ROOF SCUPPER TO LOWER ROOF CAN SEE WOOD IN PARAPET, THAT SCUPPER PASSES THRU. 3) FLEX SEAL TITE, NOT SECURED, MAX 6' LONG USE (RIDGID CONDUIT). TO KEEP WITHIN 6' LIMIT 4) LABEL NOT WHEATHER REISTANT 5) UNIT NOT LEVEL, SKIDS TO RUN PERPENDICULAR WITH RAFTERS, NOT TO BE 8' LONG, STOPS WATER FROM RUNNING OFF ROOF 6) 90 DEGREE ELBOW AN CONDENSATE 7) CONTROL WIRE CONDUIT CONNECTION NOT TIGHT 8) WORKMANSHIP DUCT CONNECTIONS 9) LABEL NOT IDENTIFIED FOR AMPERAGE |