Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM00981

Parcel: 141015730

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM00981

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
07/02/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) SECURE LIQUID TIGHT 8" FROM DISCONNECT 2) LEVEL THE UNIT 3) TURN MAXIMUM OVER CURRENT 60/60 MINIMUM CLR AMPACITY 56.1 YOU HAVE 40/40 FUSES, 50 AMP CIRCUIT FROM THE SERVICE 5) HOLE IN ROOFING AT SCUPPER PASSING THRU PARPAPET 6) 3 LABELS ON UNIT
06/30/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) NEED GFCI AT LAUNDRY SINK 2) ROOF SCUPPER TO LOWER ROOF CAN SEE WOOD IN PARAPET, THAT SCUPPER PASSES THRU. 3) FLEX SEAL TITE, NOT SECURED, MAX 6' LONG USE (RIDGID CONDUIT). TO KEEP WITHIN 6' LIMIT 4) LABEL NOT WHEATHER REISTANT 5) UNIT NOT LEVEL, SKIDS TO RUN PERPENDICULAR WITH RAFTERS, NOT TO BE 8' LONG, STOPS WATER FROM RUNNING OFF ROOF 6) 90 DEGREE ELBOW AN CONDENSATE 7) CONTROL WIRE CONDUIT CONNECTION NOT TIGHT 8) WORKMANSHIP DUCT CONNECTIONS 9) LABEL NOT IDENTIFIED FOR AMPERAGE