Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/23/2015 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 07/17/2014 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 07/17/2014 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
1. PROVIDE BALANCE REPORT AS FOLLOWS OUTSIDE AIR AS CALLED FOR ON PLANS CFM BATHROOM EXHAUST FAN CFM BATHROOM SUPPLY CFM INTER LOCK EXHAST TO RUN WHILE SUPPLY IS RUNNING TO MAINTAIN NEGATIVE AIR PRESSURE IN RESTROOM RTU FANS TO RUN CONSTINOUSLY DURING OCCUPATION |