Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/13/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/07/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) OUTLET BOXES REQUIRED FOR GARAGE LIGHTS 2) PLUMBING REQUIRED DWV TEST PER UPC 712.2 3) NO GAS TEST 4) FURNACE 'B' VENT REQUIRES 1" TO ROOF COMBUSTIBLES 5) FURANCE PLATFORM REQUIRES DRAFT STOP 6) OUTLET REQUIRED WITHIN 6' OF DOOR |
| 10/10/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |