Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 03/25/2003 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 03/21/2003 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0999*/ 1) THE GROUNDING SYSTEM REQUIRES A MINIMUM OF 2 GROUND RODS. ONLY ONE IS VISIBLE. ALSO, IF GROUND RODS ARE LAYED IN A TRENCH, AS APPOSED TO BEING DRIVEN 8' DEEP, THE TRENCH MUST BE 2.5' (30") DEEP, AND TRENCH LAYED GROUND RODS ARE ONLY TO BE USED IF IT IS IMPOSSIBLE TO DRIVE THEM VERTICALLY INTO THE GROUND 2) ALL BRANCH CIRCUITRY MUST BE IN PLACE FOR THE INTERMEDIATE INSPECTION |
| 03/10/2003 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) UNDERGROUND SCHEDULE TO PVC FROM GARAGE TO 3' FROM METER 2) OK TO BURY PVC PIPE |