Permit: T03CM00938

Parcel: 133230760

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
03/25/2003 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*
03/21/2003 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*/ 1) THE GROUNDING SYSTEM REQUIRES A MINIMUM OF 2 GROUND RODS. ONLY ONE IS VISIBLE. ALSO, IF GROUND RODS ARE LAYED IN A TRENCH, AS APPOSED TO BEING DRIVEN 8' DEEP, THE TRENCH MUST BE 2.5' (30") DEEP, AND TRENCH LAYED GROUND RODS ARE ONLY TO BE USED IF IT IS IMPOSSIBLE TO DRIVE THEM VERTICALLY INTO THE GROUND 2) ALL BRANCH CIRCUITRY MUST BE IN PLACE FOR THE INTERMEDIATE INSPECTION
03/10/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) UNDERGROUND SCHEDULE TO PVC FROM GARAGE TO 3' FROM METER 2) OK TO BURY PVC PIPE