Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/19/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) WINDOWS NOT FRAMED-IN PER PLAN 2) BOTTOM CHORD I-JOIST DAMAGED 3) NEED I-JOIST MANUFACTURER ENGINEER APPROVED DRAWINGS 4) NEED VERIFICATION OF A35'S LEDGER TO EACH STUD 5) PLAN CALLS FOR TJI 250-ASBUILT RFRI PRI70 6) INSTALL PLATE BOLTS WITHIN 12" EACH END BOTTOM PLATES 7) I-JOIST AT BEARING TO BE FILLED IN SOLIDLY (THICKNESS OF HANGER) ON BOTH SIDES 8) STOPPED INSPECTION |