Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM00931

Parcel: 141012640


Addresses:

10507 E CERULEAN WY


Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T03CM00931

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2003 ROOF NAILING Approved IVRS - Inspection 0000*/1) #2 SHEAR WALL GETS BLKS AT 4'8", YOU NEED ANOTHER ROW FOR THE UPPER JOINT IF USING 4' WIDE SHEETS; 2) SW4 SHEAR NAIL SPACING IS 4" O.C. EDGES, 12" IN FIELD; 3) PLAN CALLS FOR EXT WALL, B/PLATES TO BE ANCHORED WITH EMBED BOLTS NOT EXPANSION TYPE; 4) PLAN DOES EXPLAIN SHEAR TRANSFERS; 5) WIND BRACES TO GO TO ROOF DECK; 6) NEED TRUSS SHOP DRAWINGS ON SITE; 7) MARKED ON ROOF S/E/ WEST QUAD. IN BLACK MISSED NAILING; 8) #2.5 AT EA STUD PER DETAIL END TRUSS TO WALL NON-BEARING; INSPECTION FOR GARAGE AND MAIN HOUSE