Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
Permit Number - T03CM00931
Inspection Description - ROOF NAILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2003 | ROOF NAILING | Approved | IVRS - Inspection 0000*/1) #2 SHEAR WALL GETS BLKS AT 4'8", YOU NEED ANOTHER ROW FOR THE UPPER JOINT IF USING 4' WIDE SHEETS; 2) SW4 SHEAR NAIL SPACING IS 4" O.C. EDGES, 12" IN FIELD; 3) PLAN CALLS FOR EXT WALL, B/PLATES TO BE ANCHORED WITH EMBED BOLTS NOT EXPANSION TYPE; 4) PLAN DOES EXPLAIN SHEAR TRANSFERS; 5) WIND BRACES TO GO TO ROOF DECK; 6) NEED TRUSS SHOP DRAWINGS ON SITE; 7) MARKED ON ROOF S/E/ WEST QUAD. IN BLACK MISSED NAILING; 8) #2.5 AT EA STUD PER DETAIL END TRUSS TO WALL NON-BEARING; INSPECTION FOR GARAGE AND MAIN HOUSE |