Permit: T03CM00921

Parcel: 12709001E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM00921

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*PLEASE COMPLETE ITEMS #2,3, & 4.
2.) NEED TO SEE OFFICE FURNITURE CONNECTIONS.
05/20/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLEASE COMPLETE ITEMS 2, 3 AND 4 2) NEED TO SEE OFFICE FURNITURE CONNECTIONS
05/14/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FILL UNUSED OPENING IN PANELS.
2.) TIGHTEN LOOSE SEALTITE FITTINGS.
3.) BOND BUSHING NEEDED AT CONCENTRIC OVER 250V.
4.) PLEASE PROVIDE A COPY OF GENERATOR TEST.