Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM00921
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*PLEASE COMPLETE ITEMS #2,3, & 4. 2.) NEED TO SEE OFFICE FURNITURE CONNECTIONS. |
|
05/20/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) PLEASE COMPLETE ITEMS 2, 3 AND 4 2) NEED TO SEE OFFICE FURNITURE CONNECTIONS | |
05/14/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*FILL UNUSED OPENING IN PANELS. 2.) TIGHTEN LOOSE SEALTITE FITTINGS. 3.) BOND BUSHING NEEDED AT CONCENTRIC OVER 250V. 4.) PLEASE PROVIDE A COPY OF GENERATOR TEST. |