Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/03/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*/ 1) FLOOR DRAIN-OK, OK TO COVER 2) THIS COMPLETES ROUGH SOIL |
| 08/06/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 08/05/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NO ONE ON JOB SITE OR IN TRAILER. / REINSPECTED 2:00 PM. 1" PVC WATER SERVCE TO NEW BATHROOMS OK. TRANSITION FITTINGS OK. OK TO COVER. |
| 07/10/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) branch piping for restrooms ok, water test one riser to ten feet 2) ok to backfill |
| 07/09/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/TRANSITION BANDS- OK. OK TO COVER. |
| 07/07/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000* 6" N/H MAIN THRU BLDG WITH 4" N/H BRANCH ALL WITH HUSKEE BANDS OK. NEED TO SEE TIE-IN CONNECTIONS TO EXSISTING. USE 4 BAND SHIELDED TRANSITION COUPLING. OK TO COVER MAIN AND BRANCH. WILL INSPECT BATHROOM ROUGHS AT A LATER DATE. |