Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM00908
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2003 | ELECTRIC - FINAL | Approved | 1) OK FINAL | |
06/02/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) AN APPROVED EXTENDER RING IS NEEDED AT COMBUSTIBLE BEARING IN BATHROOM 2) PLEASE TIGHTEN WATER HEATER FLEX FITTINGS AND SECURLY ATTACH DISCONNECT TO WALL 3) RECESSED CANS TO BE ATTACHED TO GRID AND SUPPORTED WITH A SUPPORT WIRE 4) M/C CABLE TO BE SUPPORTED AS PER CODE 300-11-INDEPENDENTLY AND WITHIN 12" 5) PLEASE REVISE PLANS FOR LIGHTING 6) BOND JUNTION BOXES 250-148 7) TIGHTEN LOOSE CHORD CONNECTORS |