Permit: T03CM00900

Parcel: 12701008A


Addresses:

5255 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/08/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
10/07/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ PHARMACY AREA UNDERGROUND SOIL TEST OK. SUBJECT TO APPROVED REVISED PLANS.
09/26/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ DELI AREA - UNDERGROUND ROUGH RED LINE ON JOB. UNDERGROUND TEST ONLY, OK SUBJECT TO REVISED APPROVED PLAN.
09/22/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*
09/18/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) ROOF SECURE 2) PLEASE PROVIDE APPROVED REVISED PLANS ON ROOF DRAWING AND OVER FLOW DRAINS WILL REQUIRE TEST ON BOTH ROOF DRAINS AND OVER FLOW DRAWINGS. PLEASE DO NOT COVER-PERMIT FOR THIS WORK REQUIRED. 2ND INSPECTION ON FOOD SERVICE APPROVED. SEC VENT FOR GREASE TRAP RED LINE FOR NEW LOCATION. SA A 4 FOR ROOF DRAWINGS
09/12/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) Rooms 117, 116, 115 and 157 2) Will need revisions for drinking fountain 3) Will require test on roof drains 4) Restrooms 117, 115 AND 116
09/02/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*
08/29/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/2ND PHASE FROM BLDG DRAIN TO 3RD CO DOWN STREAM - PLEASE PROVIDE VERIFICATION OF GRADE THAT SECTION HAS BEEN TESTED. OK TO BACKFILL.
08/27/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ HCS ONLY FOR FOOD SERVICE AREA. OK TO BACKFILL.
08/25/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) HCS AT GARDEN CENTER 2) OK TO BACKFILL
08/11/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ FOOD SERVICE AREA. PARTIAL UNDERGROUND TEST ON ABS ONLY. UNDERGROUND SEE PLAN - M-ZA.
07/17/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ ROOMS # 145, 144, 139 TEST OK. RED LINE ON JOB PLEASE PROVIDE APPROVED DRAWINGS BEFORE APPROVAL IS GIVEN.
07/11/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) PLEASE PROVIDE RISER DIAGRAM FOR ROOMS #145, 144 AND 139 2) ON ROOM 139 TEST OK, OK TO COVER SUBJECT TO APPROVED. REVISED PLAN PROVIDE RISER DIAGRAM RED LINES ON JOB 3) ROOMS 145 AND 144: PROVIDE FULL SIZE CO END OF LUV AND RISER DIAGRAM
07/07/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1) UNDER FLOOR ABS DWV IN TOILET RMS #115 & #116 AND STORAGE #148- OK.WATER TEST ONE RISER TO TEN FEET. 2) OK TO COVER THIS AREA.