Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM00900
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
10/17/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
10/14/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* BOOKING ROOM, CCTV ROOM | |
09/26/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) USE OF EXTENSION CORDS FOR PERMANENT WIRING NOT ALLOWED, CORDS NOT TO PASS THROUGH CEILING TILES 2) BLANK OFF OPEN BOX OR INSTALL RECEPTACLE-FRONT COLUMN 3) PROTECT M/C CABLES AT TOP PLATES 4) GROUND BOXES AT LIGHTS IN TEMP TUNNELS | |
09/24/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS DISHWASHER AREA ROOM NUMBER 2) OK CEILING AT ENTRANCE 3) NO MORE THAN 360 DEGREE IN RUN 2) SUPPORT M/C CABLE 12" FROM BOXES 3) SUPPORT ALL BOXES WITH SUPPORT WIRES AND ATTACH TO GRID 4) INDEPENDENTLY SUPPORT M/C CABLES AS PER CODE 300.11 5) NEED TO SEE ABOVE CEILING AT ENTRANCE LATER AS DISCUSSED | |
09/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK GUEST SERVICE WALL 2) OK CASH OFFICE TO OCCUPY SUBJECT TO OTHER INSPECTORS 3) OK CANS AT ENTRY SOFFIT 4) NEED TO SEE CONNECTIONS FOR SIGN CIRCUIT WHEN SIGN INSTALLED | |
09/17/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) TIGHTEN FLEX CONNECTORS AND USE STRAPS THAT HOLD AND SUPPORT FLEX 2) PROTECT FLEX AND M/C CABLES AT STUDS 300.4 3) OK ABOVE CEILING AT FOOD COURT | |
09/05/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* FOOD COURT ROUGH WALLS OK. | |
09/03/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/OK NORTH WALL GRID LINE 5,6,7 | |
08/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK ROOM #115-117 BATHROOM LIGHTING 2) OK WALL COLUMN LINE4-5 AT EXTERIOR 3) FINISH CONDUIT STUBS | |
08/25/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
08/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) NORTH WEST SECTION OF REMODEL OK PER R. SUBA | |
08/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) JUNCTION BOX COVER MISSING 2) AN APPROVED EXTENDER RING IS NEEDED AT COMBUSTIBLE SURFACE 3) INSTALL PALTES 4) SUPPORT CONDUITS IN RAFTERS 5) GROUND JUNCTION BOXES 6) SUPPORT CABLE AT BOTH ENDS 300.11 7) OK WALLS, #148 AND 169 | |
08/15/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK 2 X 4'S 151, 152, 154-158AND 162 2) OK WALLS 104, 104A AND 110 | |
08/07/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALL AT GUEST SERVICES 2) PROTECT M/C CABLE IN STUD CHANNELS 3) ANSWERED QUESTION FOR CONTRACTOR | |
07/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK WALLS ROOMS # 115-117, 156-158, 125, 142, 139, 140. | |
07/17/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PROVIDE PROTECTION FOR CABLE WHERE LESS THAN 1 1/4" 300.4 2) SUPPORT M/C ON THE HORIZONTAL AT 6' | |
07/07/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALL ROOMS 151-156 | |
07/01/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS ROOM 162 |