Permit: T03CM00900

Parcel: 12701008A


Addresses:

5255 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM00900

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/17/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
10/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* BOOKING ROOM, CCTV ROOM
09/26/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) USE OF EXTENSION CORDS FOR PERMANENT WIRING NOT ALLOWED, CORDS NOT TO PASS THROUGH CEILING TILES 2) BLANK OFF OPEN BOX OR INSTALL RECEPTACLE-FRONT COLUMN 3) PROTECT M/C CABLES AT TOP PLATES 4) GROUND BOXES AT LIGHTS IN TEMP TUNNELS
09/24/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS DISHWASHER AREA ROOM NUMBER 2) OK CEILING AT ENTRANCE 3) NO MORE THAN 360 DEGREE IN RUN 2) SUPPORT M/C CABLE 12" FROM BOXES 3) SUPPORT ALL BOXES WITH SUPPORT WIRES AND ATTACH TO GRID 4) INDEPENDENTLY SUPPORT M/C CABLES AS PER CODE 300.11 5) NEED TO SEE ABOVE CEILING AT ENTRANCE LATER AS DISCUSSED
09/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK GUEST SERVICE WALL 2) OK CASH OFFICE TO OCCUPY SUBJECT TO OTHER INSPECTORS 3) OK CANS AT ENTRY SOFFIT 4) NEED TO SEE CONNECTIONS FOR SIGN CIRCUIT WHEN SIGN INSTALLED
09/17/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) TIGHTEN FLEX CONNECTORS AND USE STRAPS THAT HOLD AND SUPPORT FLEX 2) PROTECT FLEX AND M/C CABLES AT STUDS 300.4 3) OK ABOVE CEILING AT FOOD COURT
09/05/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* FOOD COURT ROUGH WALLS OK.
09/03/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/OK NORTH WALL GRID LINE 5,6,7
08/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK ROOM #115-117 BATHROOM LIGHTING 2) OK WALL COLUMN LINE4-5 AT EXTERIOR 3) FINISH CONDUIT STUBS
08/25/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
08/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) NORTH WEST SECTION OF REMODEL OK PER R. SUBA
08/20/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) JUNCTION BOX COVER MISSING 2) AN APPROVED EXTENDER RING IS NEEDED AT COMBUSTIBLE SURFACE 3) INSTALL PALTES 4) SUPPORT CONDUITS IN RAFTERS 5) GROUND JUNCTION BOXES 6) SUPPORT CABLE AT BOTH ENDS 300.11 7) OK WALLS, #148 AND 169
08/15/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK 2 X 4'S 151, 152, 154-158AND 162 2) OK WALLS 104, 104A AND 110
08/07/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALL AT GUEST SERVICES 2) PROTECT M/C CABLE IN STUD CHANNELS 3) ANSWERED QUESTION FOR CONTRACTOR
07/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK WALLS ROOMS # 115-117, 156-158, 125, 142, 139, 140.
07/17/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) PROVIDE PROTECTION FOR CABLE WHERE LESS THAN 1 1/4" 300.4 2) SUPPORT M/C ON THE HORIZONTAL AT 6'
07/07/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALL ROOMS 151-156
07/01/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS ROOM 162