Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) THE METER/MAIN/LOAD CENTER PANELS ARE LABELED AS 'SUITABLE FOR SERVICE EQUIPMENT ONLY'. THEY MAY NOT BE USED AS SUB-PANELS. 2) THE MIN. CLEARANCE REQUIRED IN FRONT OF ELECTRICAL LOAD CENTERS, DISCONNECTS, ETC. IS 3' IN FRONT, AND 30" TO SIDES. YOU MAY FILE AN APPEAL TO THE BLDG OFFICIAL. |
|
| 05/06/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection : The service is not per code.| 210* |
|
| 02/25/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |