Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM00890
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000*/ 1) APPROVED EXTENDER RINGS ARE NEEDED AS PER #10 PREVIOUS INSPECTION 2) A PANEL FILLER BLANK IS NEEDED-PANEL "A" 3) PLEASE SUPPLY A LETTER DELETING TRACK LIGHTING 4) PLEASE LABEL DISCONNECT IN KITCHEN AS TO WHAT IT SUPPLIES 5) SEAL ENTRANCES TO WALK IN BOXES FOR CONDENSATION 6) ROOF OK | |
06/12/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*/ 1) CLOSE EXISTING LIGHT FIXTURE WHIP CONNECTION 2) PLEASE SUPPORT NEW YOU CABLEING AS PER CODES 3) SUPPORT WIRE TO BE IN OPPISITE DIRECTIONS-ALSO FINISH INSTALLING SUPPORT WIRES 4) FINISH INSTALLATION OF TRACK LIGHTING 5) FINISH INSTALLATION OF COVER PLATES AND BOX MAKE UP 6) MAINTAIN WORKING CLEARANCES IN FRONT DISCONNECTING MEASN 110.26 7) FUSES TO BE SIZED PER CONDUCTOR AMPACITY 8) PLEASE TIGHTEN LOOSE FITTINGS 9) FINISH SUPPORTING STAND FOR DISCONNECT 10) APPROVED EXTENDER RINGS WIRE BONDED FOR BOXES WITH MORE THAN 1/4" TO FLUSH | |
06/02/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) OK WALLS SEE ATTACHED LETTER FOR FITTINGS |