Permit: T03CM00890

Parcel: 12308007C


Addresses:

3007 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM00890

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*/ 1) APPROVED EXTENDER RINGS ARE NEEDED AS PER #10 PREVIOUS INSPECTION 2) A PANEL FILLER BLANK IS NEEDED-PANEL "A" 3) PLEASE SUPPLY A LETTER DELETING TRACK LIGHTING 4) PLEASE LABEL DISCONNECT IN KITCHEN AS TO WHAT IT SUPPLIES 5) SEAL ENTRANCES TO WALK IN BOXES FOR CONDENSATION 6) ROOF OK
06/12/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) CLOSE EXISTING LIGHT FIXTURE WHIP CONNECTION 2) PLEASE SUPPORT NEW YOU CABLEING AS PER CODES 3) SUPPORT WIRE TO BE IN OPPISITE DIRECTIONS-ALSO FINISH INSTALLING SUPPORT WIRES 4) FINISH INSTALLATION OF TRACK LIGHTING 5) FINISH INSTALLATION OF COVER PLATES AND BOX MAKE UP 6) MAINTAIN WORKING CLEARANCES IN FRONT DISCONNECTING MEASN 110.26 7) FUSES TO BE SIZED PER CONDUCTOR AMPACITY 8) PLEASE TIGHTEN LOOSE FITTINGS 9) FINISH SUPPORTING STAND FOR DISCONNECT 10) APPROVED EXTENDER RINGS WIRE BONDED FOR BOXES WITH MORE THAN 1/4" TO FLUSH
06/02/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) OK WALLS SEE ATTACHED LETTER FOR FITTINGS