Permit: T03CM00882

Parcel: 141302100


Addresses:

10625 E MALTA ST


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T03CM00882

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
04/17/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*/ 1) RENAIL HANGER AT REPAIRED TRUSS 2) SHED ROO, HANGER NAILING NAILS DRIVEN IN AS TOE NAILS ARE SPLITTING THE CORNER OF THE TRUSS, NOT GETTING HOLDING FROM SHEAR
04/15/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) #3 SHEAR AT REAR CORNER, SHEAR INSIDE OF WALL EXT. IS CUT IN HALF, SHEAR TO BE CONTINOUS 2) BROKEN TRUSS MEMBER KITCHEN, HANGERS NOT NAILED CORRECTLY, ROOF IS BEING LOADED ? 3) STRAP FRONT POP OUT FOR UPLIFT DON'T HAVE CONTINOUS STUDS 4) TWO SMALL TRANSFER PANELS WERE NOT NAILED AT LAST INSPECTION
04/08/2003 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) #3 SHEAR WALL CUT UP, TOO BE SOLID UP TO TRUSS TOP CHORD, RAISE ALL SHEAR UP TO TOP CHORD 2) SHORT WIND BRACING WEST SIDE 3) SHIM 3 PT GIRDER 4) FILL NAIL HOLES FRONT H.D.'S 5) FILL ALL HOLES IN HANGERS VAULTED TRUSS 6) BROKEN TRUSS VERTICAL MEMBER IN CHANGE KITCHEN CEILINGS 7) FILL NAIL HOLES HANGERS, SMALL TWIN GIRDERS FRONT 2ND FLOOR 8) NAIL SHEAR 2 TOTAL 2ND FLOOR CLOSETS 9) TIE FRONT POP OUT TOGETHERS 10) FRONT SHED ROOF MISSED TRUSS NAILING MARKER 24' ON CENTER SOUTH EAST