Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T03CM00838
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2003 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
04/29/2003 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) INSTALL ALTERNATE HD AT FRONT DOOR 2) SECURE BACK PORCH LEDGER TO RESIST PULL-AWAY 3) INSTALL APPROVED ALTERNATE AT MISSED ANCHOR BOLTS 4) TRUSS BRACE BLOCKING MUST BE NAILED THROUGH ROOF SHEATHING 5) TRUSS CALC'S MUST BE ON SITE AT 00015 INSPECTION | |
04/28/2003 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000* |