Permit: T03CM00813

Parcel: 141305880


Addresses:

10589 E OAKBROOK ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM00813

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2003 FRAMING Approved IVRS - Inspection 0000*
04/30/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) 935 A REFEE HAS BEEN ASSESSED FOR THIS INSPECTION 2) SEE INSPECTION DATED 4/29/03 NOTHING DONE, HOUSE BEING SHEET ROCKED
04/29/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) SAN-TEE IN HALL WAY ON HORIZONTAL, WILL NEED TO RETEST VENTS 2) MOVE ELECTRICAL WIRE AWAY FROM FURNACE IN ATTIC AND ROMEX AWAY FROM CAN LIGHT UPSTAIRS ABOVE 3) OK TO INSULATE
04/28/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) NAIL PROTECT WATER LINE AT WATER HEATER PLATFORM 2) DWV'S FAILED TEST 3) USE PROPER NAIL PROTECTION AT DRYER VENT 4) SAN-TEE NOT ALLOWED ON THEIR SIDE 5) BLOCK RETURNS AT HALL AND MASTER BEDROOM 6) RE-ROUTE ROMEX FOR JACUZZI GFCI 7) MOVE ELECTRICAL WIRES AWAY FROM CAN LIGHTS AND NAIL PROTECT WITHIN 1 1/4" FROM EDGE OF STUD 8) PROVIDE HEADER AT KITCHEN BEARING WALL