Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM00813

Parcel: 141305880


Addresses:

10589 E OAKBROOK ST


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T03CM00813

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*/ 1) WILL CHECK AT NEXT INSPECTION CHANGE HEADER AT BONUS ROOM GARAGE NEED 2 X 8 2) NEED 8, A.35'S SHEAR WALL CONNECTION AT 1ST FLOOR 3) SHEAR WALL STRAPS 18A/SD4 GET CORRECT LAP 4) NAIL OFF SHEAR JOINTS AT BELLY BAND SHEAR AS PER SHEAR SCHEDULE