Permit: T03CM00807

Parcel: 136154230


Addresses:

7726 E 35TH ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/06/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) WASTE AND VENT SYSTEM IS OK 3) OVER HEAD WATER DISTRIBUTION 4) OK FOR DRYWALL
06/05/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) GAS PRESSURE TEST IS OK 2) YARD WATER LINE FROM METER TO BLDG SERVICE IS OK 3) MUST PROVIDE 18" OF COPPER BEFORE CONNECTING TO PEX AT WATER HTR 4) MUST ANCHOR GAS LINE 50 MSUT STRAP ALL HORIZONTAL VENTS 6) MUST PROVIDE A DIRECTIONAL FITTING WHEN EXTENDING A CLEAN OUT 7) 1 1/2" TRAP ARM FOR LAVATORY SINK EXCEEDS 42" 8) RETEST SYSTEM