| 04/15/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
| 04/14/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*BONDING JUMPER TO BE SIZED PER 250-102 & 250-66. FILL UNUSED IN JUNCTION BOXES ON ROOF. |