Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM00803

Parcel: 122154490

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/15/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
04/14/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*BONDING JUMPER TO BE SIZED PER 250-102 & 250-66.
FILL UNUSED IN JUNCTION BOXES ON ROOF.