Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2003 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/20/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*SOME SWITCHES NOT FRAMED CALL WHEN COMPLETE. |
| 02/18/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0145*/ 1) IN WALLS FRAMED WITH 2 X 2 METAL STUDS: THE FACE OF THE STUD MUST BE " BANG PLATED" AT THE POINT WHERE MC CABLE IS RUN THROUGH A SHED HOLE. THIS IS REQUIRED AT ANY POINT WHERE THE MC CABLE WILL BE AT 1 1/4" OR LESS FROM IT'S OUTER SURFACE TO THE SURFACE OF THE STUD. BOTH SIDES. CORRECT AND RECALL INSPECTIONS |