Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2003 | FRAMING | Approved | IVRS - Inspection 0000*STILL FRAMING WALLS. | |
| 02/19/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) PARTIAL WALLS | |
| 02/18/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*1.) PROVIDE STAMPED/APPROVED PLANS. 2.) EXISTING PENETRATIONS THROUGH FIRE WALLS MUST BE PROPERLY FIRE STOPPED. 3.) ALL EXISTING CABLE ABOVE CIELING SHOULD BE PLENUM RATED. 4.) CABLE BLOCKING FIRE DAMPER AT WEST WALL MUST BE REROUTED. 5.) I NEED TO CHECK AND SEE IF FIRE RATED OCCUPANCY SEPERATION IS REQUIRED AT NORTH WALL. 6.) OFFICE PARTITIONS OK. |