Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/17/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR C OF O |
| 07/16/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ CHECK FLEX GAS LINES- USE FULL 1/2 " OPENING AT FLARE NUT CK. MANU. INPUT ROTING ON FLEX AS NECESSARY. |
| 07/16/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ EQUIPMENT ON ROOF STILL NOT LABELED CORRECTLY. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. LEFT GAS CARD. |
| 07/14/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) EXTEND SEWER VENTS 2' ABOVE AIR INTAKES. 2) GAS FLEX CONNECTORS NOT ADEQUATE SIZE. 3) PERMANENTLY LABEL EQUIP. ON ROOF. 4) PROVIDE CANVAS SUN-SHIELD. 5) SEAL AROUND OSA INTAKES. 6) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN, NOT SUPPLY DUCTS. |