Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM00762

Parcel: 13505149N


Addresses:

2401 S WILMOT RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/17/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) OK FOR C OF O
07/16/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ CHECK FLEX GAS LINES- USE FULL 1/2 " OPENING AT FLARE NUT CK. MANU. INPUT ROTING ON FLEX AS NECESSARY.
07/16/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ EQUIPMENT ON ROOF STILL NOT LABELED CORRECTLY. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. LEFT GAS CARD.
07/14/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) EXTEND SEWER VENTS 2' ABOVE AIR INTAKES. 2) GAS FLEX CONNECTORS NOT ADEQUATE SIZE. 3) PERMANENTLY LABEL EQUIP. ON ROOF. 4) PROVIDE CANVAS SUN-SHIELD. 5) SEAL AROUND OSA INTAKES. 6) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN, NOT SUPPLY DUCTS.