Permit: T03CM00756

Parcel: 11006015C

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
09/08/2003 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*/ CHECKED FIRE DAMPERS. OK TO COVER.
09/03/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) ALL WOOD FRMED FIRE DAMPER OPENINGS MUST BE WRAPPED WITH 5/8" SHEET ROCK. NEED TO SEE OPENINGS PRIOR TO INSTALLING DAMPERS. CONNECTIONS WITH RIGID DUCT REQUIRED TO HAVE ACCESS DOORS. FLEX DUCT CONNECTIONS USE A REMOVABLE BAND FOR ACCESSING DAMPER