Permit: T03CM00748

Parcel: 111060540

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/08/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
12/02/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) LETTER NOT ON SITE
11/25/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) PLEASE PROVIDE A LETTER AUTHORIZING USE OF ALUMINUM FEEDER CONDUCTORS 3) OK WALLS SUBJECT TO LETTER
11/24/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
11/21/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) STILL CANNOT LOCATE APPROVED PLANS 2) SUPPORT CABLES ABOVE PANELS 3) SUPPORT NM CABLE WITHIN 12" OF BOXES/EXHAUST FANS 4) PLEASE EXTEND BOXES BEYOND FOAM FOR STUCCO 5) PROTECT CONDUCTORS INSIDE BOXES 370.43 6) FILL UNUSED PANEL OPENING-NOT WITH SCREWS
11/19/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999* NO APPROVED PLANS ON SITE