Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/09/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/10/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CUT SEWER CLEANOUT TO GRADE 2) LABEL ELECTRIC PANEL CIRCUITS SERVED 3) POST ADDRESS NUMBERS ON HOUSE 4) COMPLETE GRADING TO SLOPE AWAY FROM HOUSE 5) INSTALL RECEPTACLES UNDER SINK 6) MAINTAIN MINIMUM 6" CLEARANCE FRONT OF FURNACE 7) INSTALL CLEAN OUT UNTO SINK 8) ELEVATE AND SECURE DISHWASHER DRAIN HOSE 9) INSTALL VACCUM BREAKER HOSE BIBS 10) INSTALL GAS COCK AND PLUG AT DRYER AND RANGE 11) NEED ACCESS INTO REAR UTILITY ROOM 12) NEED INSULATION AND STUCCO CERTIFICATES FROM INSTALLERS 13) STOPPED INSPECTION 14) INSTALL DRIP LEG GAS LINES FURNACE AND WATER HEATER PIPING 15) INSTALL DOUBLE WALL VENT PIPE FURNACE FLUE |