Inspection History: ELECTRIC - FINAL
Permit Number - T03CM00732
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ NOTES: HANGER AND BLDG WEST OF HANGER 1) INSTALL PERMANENT ADDRESS LABELS ON SERVICE ENCLOSURES 2) ALL OUTSIDE RECEPTACLES MUST BE GFCI PROTECTED 3) FEEDER TAPS AT MAINT. HANGER NOT PER CODE. MULTIPLE TAPS OVER 10' LONG MUST COMPLY WITH ART. 240 N.E.C. 4) RE-SUPPORT DISCONNECT SWITCH AND CONDUIT SUPPORTS AT MAINT. HANGER AT POLE SOUTHWEST CORNER. 5) TRANSFORMERS NOT BONDED PROPERLY. BOND PER ART. 250 N.E.C. (3 TOTAL) 6) SUPPORT CONDUITS PER N.E.C. RELABEL DISCONNECTS SWITCH ? 7) ID CIRCUIT BREAKERS, LABEL LOAD CENTER BREAK PATIO AND SUPPORT UF CABLE FOR SECURITY LIGHT 8) RE-SUPPORT CONDUIT, LABEL PANEL, DISCONNECT OR ABANDON UNUSED FEEDERS, SOUTHEAST CORNER OUTSIDE HANGER WALL OF HANGER 9) PLUG UNUSED KO'S IN DISCONNECT SWITCHES EAST OUTSIDE WALL OF HANGER 10) SUPPORT J-BOXES AT NOSE DOCK. SUPPORT CONDUIT WITHIN 3' PER N.E.C. 11) ALL CONDUIT IN MAINT. HANGER TO BE SUPPORTED N.E.C. 12) SUPPORT CONDUITS PER-N.E.C. AT HAYBARN EAST OF HANGER. BROKEN FITTINGS, ON BONDED TRANSFORMER 13) SMALL HANGER, SEE OTHER BLDG VIOLATIONS |