Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM00693
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
03/03/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ BOX BEHIND FIXTURE TO BE RATED FOR OUTDOORS, ALSO CAP OUTLET WHERE OTHER FIXTURE REMOVED. | |
03/02/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ NOT READY PER DWIGHT - 326-3200. | |
02/25/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) BATTERY BACK UP LIGHT NOT WORKING AND NOT ON CIR 13 OF NEW PANEL | |
02/24/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) WEST FEM LIGHT OUTSIDE BY STAIRS DOES NOT COME ON WITH FEM CIR WHEN POWER OFF CIR 13 | |
02/17/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) "FEM" LIGHTS TO BE CONNECTED TO REMOTE EM BALLAST AS PER PLAN. LIGHTS NOT WORKING AT THIS TIME | |
02/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) PANEL MP NEEDS A PANEL SCHEDULE 2) EAST SIDE RAMP BEM AND LIGHT FIXTURE ON WALL TO BE NIGHT LIGHT 3) EHT LIGTH AND EB EMERGENCY LIGHT BY NORTH STAGE DOOR MISSING 4) EB EM LIGHT MISSING BY WEST DOOR EXIST MULTI PURPOSE TO NEW 5) SMOKE DETECTOR SYSTEM MISSING ON SMALL A/C VERIFY 6) REMOTE BATTERY PACK ABOVE CEILING 7) PERMANENTLY MARK SW GEAR-200A FUSE PANEL MP 8) IF NEW 100 AMP DISCONNECTS FOR NEW 5 TON A/C'S OMITTED PLEASE VERIFY PER LETTER 9) ROOF OK LETTER ON UFER OK 10) LETTER OJN PULL BOX STILL REQUIRED (TO SIZE #5) |