Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T03CM00693
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000*/ 1) PANEL MP NEEDS A PANEL SCHEDULE. 2) EAST SIDE RAMP BEM AND LIGHT FIXTURE ON WALL TO BE NIGHT LIGHT. 3) EXIT LIGHT AND EB EMERGENCY LIGHT BY NORTH STAGE DOOR MISSING. 4) EB EM LIGHT MISSING BY WEST DOOR. EXIST MULTI PURPOSE TO NEW. 5) SMOKE DETECTOR SYSTEM MISSING ON SMALL A/C VERIFY. 6) REMOTE BATTERY PACK ABOVE CEILING. 7) PERMANENTLY MARK SW GEAR - 200 AMP FUSE 'PANEL MP'. 8) IF NEW 100 AMP DISCONNECTS FOR NEW 5 TON AC'S OMMITTED PLEASE VERIFY PER LETTER. / ROOF OK. LETTER ON UFER OK. LETTER ON PULL BOX STILL REQUIRED, AS TO SIZE NUMBERS. | |
12/02/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*/ 1) OK CONDUIT FROM PULL BOX TO SES 2) PLEASE VERIFY FROM ENGINNER IF A #3 PULL BOX IS LARGE ENOUGH TO MAINTAIN WIRE BENDING RADIOUS | |
11/26/2003 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*/ 1) WHERE IS PULL BOX PER PLANS AND LETTER FROM MCGETRICK (JULY 10, 2003) | |
07/07/2003 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
07/03/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*FROM PREVIOUS 50' ( OF 6-30-03) TO W/IN SERVICE FENCE/INC. PLEASE WILL NEED LETTER OF ???? OF PULL BOX AND THE RE CONFIGURATION OF THE LINE OF EXCAVATION. | |
06/30/2003 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*/ 1) OK 2 1/2" PVC 50' OUT FROM ADDITION |