Permit: T03CM00693

Parcel: 110120010


Addresses:

5330 E GLENN ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T03CM00693

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*/ 1) PANEL MP NEEDS A PANEL SCHEDULE. 2) EAST SIDE RAMP BEM AND LIGHT FIXTURE ON WALL TO BE NIGHT LIGHT. 3) EXIT LIGHT AND EB EMERGENCY LIGHT BY NORTH STAGE DOOR MISSING. 4) EB EM LIGHT MISSING BY WEST DOOR. EXIST MULTI PURPOSE TO NEW. 5) SMOKE DETECTOR SYSTEM MISSING ON SMALL A/C VERIFY. 6) REMOTE BATTERY PACK ABOVE CEILING. 7) PERMANENTLY MARK SW GEAR - 200 AMP FUSE 'PANEL MP'. 8) IF NEW 100 AMP DISCONNECTS FOR NEW 5 TON AC'S OMMITTED PLEASE VERIFY PER LETTER. / ROOF OK. LETTER ON UFER OK. LETTER ON PULL BOX STILL REQUIRED, AS TO SIZE NUMBERS.
12/02/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK CONDUIT FROM PULL BOX TO SES 2) PLEASE VERIFY FROM ENGINNER IF A #3 PULL BOX IS LARGE ENOUGH TO MAINTAIN WIRE BENDING RADIOUS
11/26/2003 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*/ 1) WHERE IS PULL BOX PER PLANS AND LETTER FROM MCGETRICK (JULY 10, 2003)
07/07/2003 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*
07/03/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*FROM PREVIOUS 50' ( OF 6-30-03) TO W/IN SERVICE FENCE/INC. PLEASE WILL NEED LETTER OF ???? OF PULL BOX AND THE RE CONFIGURATION OF THE LINE OF EXCAVATION.
06/30/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK 2 1/2" PVC 50' OUT FROM ADDITION