Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2003 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000*CORRECTION MADE OK PLUMBING DELETED THAT WAS NOT APPROVAL PLUMBER TO INSTALL APPROVED ABS PERM CAP AT DELETION. CLOSET FLANGE OK OK TO COVER WALLS. |
|
| 04/30/2003 | PLUMBING - GAS PRESSURE TEST | Partial Approval | 1.) HAVE PLUMBER READ PLUMBING GENERAL NOTES #4. HANGERS AND SUPPORTS. 2.) HAVE PLUMBER READ PLUMBING GENERAL NOTE #14 NO PROVISION MADE FOR INSULATION. 3.) PLUMBER MAY NOT INSTALL ADDITIONAL PLUMBING MUST BE INSTALLED PER APPROVED PLAN. 4.) GUAGE FOR GAS PRESSURE TEST TO BE IN ONE POUND INCREMENTATION OR LESS. 5.) MAY NOT REDUCE TRAP ARM SIZE 6.) MAY NOT RUN 2" TRAP ARM TO LAVATORY 7.) NO WATER TEST ON ABS. |