Permit: T03CM00684

Parcel: 113081970

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/11/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/08/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) THE GROUND WIRE MUST BE IN THE " POCKET " SIDE OF THE GROUND ROD CLAMP. 2) BOTH ENDS OF THE OFF SET NIPPLE BETWEEN SERVICE METER CAN AND SUB-PANEL MUST BE BONDED. ADD BOND BUSHING AND WIRE