Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
11/21/2003 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection 0000*
11/20/2003 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*/ 1) PRESSURE READ 31 POUNDS ONLY-REPRESSURIZE 2) IF PRESSURE OK ON FRI-DROP GAS CARD
11/17/2003 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*/ 1) NON-METALLIC GAS PIPING MUST BE 18" DEEP 2) PRESENTLY THERE ARE SEVERAL AREAS THAT ONLY HAVE 12" OF DEPTH
11/14/2003 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*/ 1) NO ONE PRESENT TO PROVIDE ACCESS. PLEASE RECALL WHEN ACCESS IS AVAILABLE