Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/13/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR C OF O. |
| 10/31/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CONDENSOR STILL OVERFUSED 2) MARK DATA PLATE RTU-4 WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY 3) RECALL FOR INSPECTION |
| 10/24/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PERMANENTLY LABEL A/C EQUIPMENT 2) LABEL DATA PLATES WITH PROPER HEAT STRIP INSTALLED 3) CONDENSORS OVERFUSED. OK FOR TEMP C OF O |