Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/14/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* FINISH #2 ON PREVIOUS INSP |
| 11/12/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) EMERGENCY LIGHT TO BE EFFECTIVE. 2) TIGHTEN FLEX & NIPPLE FITTINGS FOR NEON. 3a) INSTALL GTO CABLE FULLY INTO ELEC TO BIT CUP. 4) FURNISH POWER OUT TO MONUMENT & SIGN. |
| 10/31/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK PHARMACY, TRAINING ROOM, BATHROOMS, BREAKROOM, STUCK ROOM-FINAL 2) OK TEMP C OF O TO STOCK ONLY SUBJECT TO DETERMINATION OF STEVE LONG 3) 1 CONDUCTOR PER SCREW IN PLUG MOLDS 4) CHECK CONNECTIONS TO FLOOR BOXES |
| 10/29/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) OK REFRIGERATION COOLERS, OK EAST WALL LIGHTING IN DISPLAY GONDULAS 2) USAGE OF CORD PER 400.7 AND 400.8 TO ALLOW ABILITY TO GONDULA-NOT ALLOWED FOR GONDULA POWER 3) SUPPORT FLEX CONDUIT AS PER CODES 3) APPROVED EXTENDER RINGS ARE NEEDED WHERE NOT FLUSH AT COMBUSTIBLES OR 1/4" AT NON COMBUSTIBLES. METAL NOT APPROVED 5) NEW DATA CANNOT LAY ON GRID 6) JUNCTION BOXES TO BE ACCESSIBLE |
| 10/16/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TEMP POWER FOR TEST 2) A LABEL STATING 1000 AMP FUSES ONLY HAS BEEN PLACED ON EQUIPMENT |
| 10/14/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) COMPLETE #8 OF PREVIOUS INSPECTION-CHECK WITH MANUFACTURER. IF A NEW SWITCH OR LABEL IS CHANGED EQUIPMENT WILL NEED A FIELD EVALUATION LETTER SUBMITED BY 3RD PARTY TESTING 2) RECEIVED LETTER FOR TORQUE |