Permit: T03CM00671

Parcel: 13305054K


Addresses:

8705 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM00671

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/19/2003 ELECTRIC - ABOVE CEILING Approved
10/07/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) OK SALES FLOOR, PHARMACY, LEARNING CENTER, READING AREA AND ENTRY WAY TO STORE ROOM 2) FINISH INSTALL OF BOXES AND MAKE-UP
10/02/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) ATTACH FIXTURES TO GRID 410.16 2) M/C CABLE TO BE INDEPENDENTLY SUPPORTED 300.11 3) ALL BOXES IN CEILING TO HAVE WIRE SUPPORTS 4) WE HAVE CONDUCTOR FILL PROBLEMS IN GUTTERS 374.5 5) GUTTER LIST MAX WIRE SIZE AS #3 6) TIGHTEN LOOSE LUGS 7) NEUTRAL DISCONNECT LINK NOT CONNECTED 8) MAIN DISCONNECT MISLABLED 480V-WE HAVE 208Y/120V SYSTEM 7) PLEASE PROVIDE A LETTER FOR TORQUE OF SERVICE
09/17/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) OK DRIVE THROUGH CEILING
09/11/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) SOFFIT AREA OUTSIDE FRONT EXCEPT ENTRANCE. LAST POLE BASE NORTH SIDE OF PARK LOT. OK TO COVER