Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM00671
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2003 | ELECTRIC - ABOVE CEILING | Approved | ||
| 10/07/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) OK SALES FLOOR, PHARMACY, LEARNING CENTER, READING AREA AND ENTRY WAY TO STORE ROOM 2) FINISH INSTALL OF BOXES AND MAKE-UP | |
| 10/02/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) ATTACH FIXTURES TO GRID 410.16 2) M/C CABLE TO BE INDEPENDENTLY SUPPORTED 300.11 3) ALL BOXES IN CEILING TO HAVE WIRE SUPPORTS 4) WE HAVE CONDUCTOR FILL PROBLEMS IN GUTTERS 374.5 5) GUTTER LIST MAX WIRE SIZE AS #3 6) TIGHTEN LOOSE LUGS 7) NEUTRAL DISCONNECT LINK NOT CONNECTED 8) MAIN DISCONNECT MISLABLED 480V-WE HAVE 208Y/120V SYSTEM 7) PLEASE PROVIDE A LETTER FOR TORQUE OF SERVICE | |
| 09/17/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) OK DRIVE THROUGH CEILING | |
| 09/11/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) SOFFIT AREA OUTSIDE FRONT EXCEPT ENTRANCE. LAST POLE BASE NORTH SIDE OF PARK LOT. OK TO COVER |