Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM00671
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* BARREL ROUGH | |
| 09/08/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ NOTES 1) OK 3-1/2" CONDUIT FEEDERS UP TO MEZZ. OK WALLS IN MEZZ. | |
| 08/29/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK WALLS AND HARD CEILING NORTH OF COLUMN #4, EXCEPT FEEDER CONDUIT. | |
| 08/25/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) TEMP SERVICE: A) A PROPER SUPPORT IS NEEDED FOR RISER B) CABLE TO BE 18" IN DEPTH 300.5 C) FILL UNUSED OPENING IN PANEL 110.12 D) BOND RISER 250.94 E) LABEL BREAKERS F) WALLS: SUPPORT CONDUIT AS PER CODE 3' FROM FLOOR AND BOXES 2) OK EXTERIOR WALLS EXCEPT NORTH EAST CORNER 3) NO MORE THAN 360 DEGREE IN A CONDUIT RUN |