Permit: T03CM00662

Parcel: 12510006A


Addresses:

3699 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM00662

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2004 MECHANICAL - ABOVE CEILING Approved
04/23/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*/ WANT TO SEE A SMOKE ALARM ENERGIZED AND EXERCIZED PRIOR TO FINAL.
04/02/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ CHECK VALVES IN SUSPENDED AIR HANDLERS SMOKE ALARMS PROGRESSING IN PROPER LOCATIONS.
03/29/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
03/24/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ IMC, SMOKE ALARMS, SEE 606.2.1, LOCATE IN RETURN AIR DUCTS
03/19/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) EXHAUST HOOD, STAINLESS STEEL, 16 GA VTR. COOKING APP. PIZZA OVEN. TYPE II SUFFICES. CHECK SPECS IF TYPE I IS BEING SUPPLIED FOR FUTURE
03/15/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ PARTIAL INSP. ON CONDENSATE DRAIN LINES. PROVIDE ADEQUATE SLOPE ON N.E. SECTION. STILL NEED TO SEE DRAIN LINES FROM FAN COIL PUMPS. OK FOR CEILING TILES IN MAIN SALES FLOOR ONLY. LEAVE OUT UNDER ALL DUCT SMOKE DETECTORS. OK FOR TEMP POWER FOR TESTING.
02/24/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) PARTIAL INSPECTION ON SUSPENDED ROUGH DUCT. OK TO PROCEED