Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM00662
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2004 | PLUMBING - FINAL | Approved | CORRECTIONS HAVE BEEN MADE. FINAL OK. | |
06/14/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ CORRECTIONS HAVE BEEN MADE AS PER LAST REQUEST EXCEPT FOR BACKFLOW DEVICE IN GARDEN CENTER NOT INSTALLED AS PER APPROVED PLAN. PLEASE PROVIDE APPROVED REVISED PLAN OR INSTALL AS PER APPROVED PLAN. | |
06/09/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) ACCESS TO TRAP PRIMER-RESTROOM FRONT ROOM 127. 2) RP REQUIRED FOR ? NOT OVER 5'-0" 3) ICE MAKER DOUBLE CHECK NOT OVER 5'-0" 4) BACK FLOW DEVICE FOR COFFEE MAKERS 5) EACH ICE UNIT WILL NEED IT'S OWN BACKFLOW DEVICE 6) SODA-NONCARB-WILL NEED IT'S OWN DEVICE | |
05/26/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ PLEASE CALL AGAIN WHEN READY. |