Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM00662

Parcel: 12510006A


Addresses:

3699 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM00662

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2004 PLUMBING - FINAL Approved CORRECTIONS HAVE BEEN MADE. FINAL OK.
06/14/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ CORRECTIONS HAVE BEEN MADE AS PER LAST REQUEST EXCEPT FOR BACKFLOW DEVICE IN GARDEN CENTER NOT INSTALLED AS PER APPROVED PLAN. PLEASE PROVIDE APPROVED REVISED PLAN OR INSTALL AS PER APPROVED PLAN.
06/09/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) ACCESS TO TRAP PRIMER-RESTROOM FRONT ROOM 127. 2) RP REQUIRED FOR ? NOT OVER 5'-0" 3) ICE MAKER DOUBLE CHECK NOT OVER 5'-0" 4) BACK FLOW DEVICE FOR COFFEE MAKERS 5) EACH ICE UNIT WILL NEED IT'S OWN BACKFLOW DEVICE 6) SODA-NONCARB-WILL NEED IT'S OWN DEVICE
05/26/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ PLEASE CALL AGAIN WHEN READY.