Permit: T03CM00587

Parcel: 133325270


Addresses:

105 N DIXIE AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/29/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
10/28/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ CIRCUIT TO CONDENSOR IS OVERSIZED AT 50 AMP. 40 AMP IS MAX. EVERYTHING ELSE IS OK. RECALL FOR INSPECTION. FAN COIL IS ALSO TOO LARGE - 30 AMPS IS MAX.