Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/29/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/28/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ CIRCUIT TO CONDENSOR IS OVERSIZED AT 50 AMP. 40 AMP IS MAX. EVERYTHING ELSE IS OK. RECALL FOR INSPECTION. FAN COIL IS ALSO TOO LARGE - 30 AMPS IS MAX. |