Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/26/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/24/2003 |
FRAMING |
|
Denied |
1) NAIL SHEAR PANEL TO CONFORM WITH APPROVED DRAWINGS |
| 03/21/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) ITEMS NOT CORRECTED |
| 03/20/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) 1ST FLOOR LAV TRAP ARM EXCEEDS 42" AND WEIR HIGHER VENT 2) NO DWV WATER TEST 3) IMPROPER PEX COUPLING AT SERVICE ENTRANCE MORE THAN 1/16" FROM STOP 4) FLOOR JOIST NOT BEARING ON GLU LAM BEAM DINING ROOM AND HEADER 5) PEX NOT ALLOWED WITHIN 12" OF CAN LIGHT KITCHEN 6) NAIL PROTECT WIRES WITHIN 1 1/4' OF STUD SURFACE 7) 2ND FLOOR BOTTOM PLATE DOES NOT BEAR ON FLOOR-MANY PLACES 8) PLATES MUST BEAR ON HEADERS AND HEADERS ON TRIMMERS 9) PROVIDE SHEAR PANELS FRONT BEDROOM |
| 03/17/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) COMPLETE LATH 1ST |