Permit: T03CM00564

Parcel: 135076150


Addresses:

2076 S CUTTER LN


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM00564

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2003 FRAMING Approved IVRS - Inspection 0000*
04/25/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*
04/24/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*
04/21/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE DWV TEST AT 1ST FLOOR 2) MOVE ROMEX AT WATER HEATER FLUE 3) STUCCO INCOMPLETE 4) SECURE PLUMBING ABS THRU-OUT
04/18/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) LEAK IN TUB DRAIN-NORTH OF PATIO DOOR-RE-DO DWV (TUB WATER IS BELOW OVERFLOW) 2) NEED WATER PRESSURE TEST 3) SECURE GAS PIPE AT STOVE 4) SUPPORT VENT 90 DEGREE AT ROOF NEXT TO HOT WATER FLUE 5) FHA STRAP TOP PLATES AT PLUMBING VENT CUT IN NORTH BEDROOM 6) REPAIR TOP PLATE AT FURNACE GAS PIPE